开云体育

ctrl + shift + ? for shortcuts
© 2025 Groups.io
Date

Re: NOS cermic-metal tube burn in

Hsu
 

开云体育

Screen PS V=350V,
?anode PS V=2kV.
?? they are ?in Collins KWS-1.
???? My friend have been burn in for 2 hours, the bias crrrent has ben increase to 100ma, and can get more
(400-500ma) current, I think the tubes?are good.
?????? Hsu?

----- Original Message -----
Sent: Tuesday, November 14, 2006 2:20 AM
Subject: Re: [ham_amplifiers] NOS cermic-metal tube burn in

What is the screen PS V?
What is the anode PS V?

What Class?

On Nov 13, 2006, at 7:34 AM, Hsu wrote:

> Hi, There are two Chinese FU-251F(4CX250B) cermic-metal tubes, they
> are new but storge for very long time. The output power only
> 200-250W( a pair), Could someone cal tell me how to solve this
> problem?Is it means I have to drop them in the junk box?
> 73! Hsu
>
>

R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


Re: Pseudo Grid Current

pentalab
 

--- In ham_amplifiers@..., jmltinc@... wrote:

OK, I need professional help.

I got a basket-case Henry 3K Ultra some time ago and have been
repairing in
my spare time. Amongst the defects it had, was a plate choke flash-
over. This
took out the .5 ohm (20 watt?) resistor and diode (on the power
supply) that
hold the B- to near ground potential. It also took out a small
(.1?) cap at the
plate current meter (in the desk console). The schematic is not
correct for
this unit and Henry was no help. I did what I think is correct.
#### Whoa. I'll be damned if I can find my henry 3k/8k ultra
manual. IF u had a flash over between plate choke and
chassis.... it would short out the undersized safety diode
between chassis and B- When that happens, the neg of the
grid shunt is now directly in parallel [via the chassis, and then
the shorted safety diode] with the neg of the plate meter.
The pos of the plate meter is normally directly tied to the pos
of the grid meter. You now have a condition, whereby both meter's
are in parallel..... so the grid meter will now read plate current!

### Now u know why I always install a HV fuse in the B+ lead !
You may well have damaged some diodes in the FWB diode assy too...
[waiting for the slo breaker in the 240 v line to open up].

### Henry, in their infinite wisdom, installed the glitch R in
the B- lead.... not a smart move... since that will allow the fil
xfmr to spike to full anode v, etc.

### IF u want to fix this right.... I'd install a 50 ohm-50w
wire wound in the B+ lead. [or at least a 25 ohm-25 watt, wirre
wound] I'd also install a HV fuse just PRIOR to the glitch.
reason is... if glitch R ever exploded.. and pieces of it hung
down and touched chassis.... you want the HV fuse to be on the
inboard side of the glitch R.... so it will blow open.. shutting
every thing down.

### I'd also install some RVS connected diodes, either 6A10 [1
kv -6A]... or PARALLELED 1N5408's [1 kv- 3A] between chassis,
and B- and also some more RVS connected diodes across
BOTH meter's movements. Myself, I use 3 x paralleled 6A10's in
each direction..... 6 in total.... 1200A surge.[between chassis
and B-].... and just 2 paralleled diodes, in each direction, RVS
connected... across EACH meter. The surge rating on the diodes
should be plenty high enough so they never get stressed... and never
short out.... and never have to be replaced. .... then u wouldn't be
having this problem in the 1st place. [Ameritron does the same
thing with their one and only underated safety diode between
chassis and B-..... "check to see if diode XXX is shorted"... IMO,
they shoulda just sized the safety diodes right the 1st time...
since they are dirt cheap]

### The kicker here is....IF u blow any HV fuse.... ur grid
current is gonna go sky high..... so now u need a simple FAST
grid fuse, 3agc type..... wired between chassis.. and grid
shunt. [both the 3k + 8k have NO grid overcurrent protection at
all]

### If u want.... install a 3agc- CATHODE fuse in the CT of the
fil xfmr... either just b4, or just after the bias diodes [used
for setting ZSAC] . Install a 100 k, or better yet.. a pair of
100 k MOF 2-3 watt resistors across the cathode 3agc fuse
holder. Any Cathode fast fuse has to handle the SUM of normal
anode current PLUS grid current.

### when config like this..... if u remove [or blow open] either
the grid fuse... OR the cathode fuse... INPUT swr will rise to
infinity..... shutting down ur xcvr.

### You may well have to get in their.. and draw out the existing
circuit by hand.... then compare it to a standard config. I'll
look for my 3 k ultra manual later on... had it in a binder.

### also... in the combo 3k/8k manual [pretty sure the 3k ultra is
the same setup], Henry used a 2x piece plate choke setup.... I have
the RFC's from the 8 k ultra. The big one is 24 ga magnet
wire , wound on a 1" diam solid teflon rod... and measures 180
uh. The small one is just 20 uh, wound with 18 ga wire. The
large choke was shorted out on the high bands,14-30 mhz...with a HV
solenoid relay.

### You are gonna have to find the reason for the flash over... it
might be the large choke shorting relay.... it might also be the
paralleled bypass caps at the base of the large plate choke, which
on the 8k are 2-3 x 4700 pf caps + 2-3 500 pf doorknobs.


## The amp works as is.. with 1500w out. So this is just a
metering problem.. cuzed by a shorted diode.... caused by a HV arc
to chassis...... which if the amp was config correctly.... should
have just taken out the HV fuse... then the grid fuse a split
2nd later.

Later.... Jim VE7RF



Now my problem:

The grid meter show excessive current. I am convinced this is
not "grid
current", but plate current. See the table below for results:

Grid Current Plate Current Power
Out

Amp on, not keyed: 75ma 0ma 0W
Amp keyed, no drive 225ma 150ma 0W
Amp keyed, 50W drive >1,000ma 875ma 1,500W

Notice grid current w/ no excitation and how the grid current
follows the
plate current. Hmmm...

If I draw out how the metering is wired it looks right. For the
grid meter,
here is a .5 ohm resistor shunt from ground to cathode with a 470
ohm, 3 Watt
series dropping resistor from the cathode side of the shunt to the
grid meter.
(The other side of the meter is grounded).

For the plate meter, there are two series .1 ohm shunt resistors
from the
glitch R to the cathode. The meter is connected across this with a
150 ohm series
dropping resistor between it and the shunt R / glitch R connection.

Any ideas?

Thanks
-John


Re: Pseudo Grid Current

 

On Nov 14, 2006, at 6:04 PM, jmltinc@... wrote:

OK, I need professional help.

I got a basket-case Henry 3K Ultra some time ago and have been repairing in
my spare time. Amongst the defects it had, was a plate choke flash- over. This
took out the .5 ohm (20 watt?) resistor and diode (on the power supply) that
hold the B- to near ground potential. It also took out a small (. 1?) cap at the
plate current meter (in the desk console). The schematic is not correct for
this unit and Henry was no help. I did what I think is correct.

Now my problem:

The grid meter show excessive current. I am convinced this is not "grid
current", but plate current. See the table below for results:

Grid Current Plate Current Power Out

Amp on, not keyed: 75ma 0ma 0W
Amp keyed, no drive 225ma 150ma 0W
Amp keyed, 50W drive >1,000ma 875ma 1,500W

Notice grid current w/ no excitation and how the grid current follows the
plate current. Hmmm...

If I draw out how the metering is wired it looks right. For the grid meter,
here is a .5 ohm resistor shunt from ground to cathode with a 470 ohm, 3 Watt
series dropping resistor from the cathode side of the shunt to the grid meter.
(The other side of the meter is grounded).

For the plate meter, there are two series .1 ohm shunt resistors from the
glitch R to the cathode. The meter is connected across this with a 150 ohm series
dropping resistor between it and the shunt R / glitch R connection.

Any ideas?
John = The first thing I would do is to connect two back to back 3A diodes across each meter movement to protect them from possible damage. The second thing would be to check the calibration of all metered functions against a calibrated DMM, and do whatever it takes to make them read accurately. Third, I would add a suitable glitch-R in the HV+ lead.

Thanks
-John

R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


Pseudo Grid Current

 

OK, I need professional help.

I got a basket-case Henry 3K Ultra some time ago and have been repairing in
my spare time. Amongst the defects it had, was a plate choke flash-over. This
took out the .5 ohm (20 watt?) resistor and diode (on the power supply) that
hold the B- to near ground potential. It also took out a small (.1?) cap at the
plate current meter (in the desk console). The schematic is not correct for
this unit and Henry was no help. I did what I think is correct.

Now my problem:

The grid meter show excessive current. I am convinced this is not "grid
current", but plate current. See the table below for results:

Grid Current Plate Current Power Out

Amp on, not keyed: 75ma 0ma 0W
Amp keyed, no drive 225ma 150ma 0W
Amp keyed, 50W drive >1,000ma 875ma 1,500W

Notice grid current w/ no excitation and how the grid current follows the
plate current. Hmmm...

If I draw out how the metering is wired it looks right. For the grid meter,
here is a .5 ohm resistor shunt from ground to cathode with a 470 ohm, 3 Watt
series dropping resistor from the cathode side of the shunt to the grid meter.
(The other side of the meter is grounded).

For the plate meter, there are two series .1 ohm shunt resistors from the
glitch R to the cathode. The meter is connected across this with a 150 ohm series
dropping resistor between it and the shunt R / glitch R connection.

Any ideas?

Thanks
-John


Re: [Amps] Variable capacitors and 4CX250B FS

Hsu
 

Sorry, make incorrect, WxHxD not include shaft's length.

----- Original Message -----
From: "Hsu" <Jbenson@...>
To: <ham_amplifiers@...>
Cc: <amps@...>
Sent: Tuesday, November 14, 2006 4:04 PM
Subject: [Amps] Variable capacitors and 4CX250B FS



I have 20 NOS Variable capacitors, one is 1400PF/1kV(0.65mm spacing ), another one is 200PF/3kV(2mm spacing ).
a set of capacitors(1400P/1kV+200P/3.5kV)=$80, include shipping.WxHxD=92mmx87mmx85mm( include shaft's length),weight=550g , a pair NOS EIMAC 4CX250B in papaer box=$150 I pay the shipping cost.
73! Hsu
_______________________________________________
Amps mailing list
Amps@...


Variable capacitors and 4CX250B FS

Hsu
 

I have 20 NOS Variable capacitors, one is 1400PF/1kV(0.65mm spacing ), another one is 200PF/3kV(2mm spacing ).
a set of capacitors(1400P/1kV+200P/3.5kV)=$80, include shipping.WxHxD=92mmx87mmx85mm( include shaft's length),weight=550g , a pair NOS EIMAC 4CX250B in papaer box=$150 I pay the shipping cost.
73! Hsu


Re: Inrush filament current protection

Phil Clements
 

I looked. In our breaker box, all the ground wires and all the
Neutral wire connecct in one bus bar. How would it be different if
there were two bus bars that are connected by a bus-wire?

No electrical difference here; but if the breaker box is to be used as
a sub-panel, you need seperate bus bars for the neutrals and grounds
with a removable shorting strap between the two. Only in the main
service entrance panel do the neutrals and grounds all strap together.
I guess a few bucks are saved by leaving out the strap and insulation
for the two bus bars if one has no intention of ever changing a main
panel over to a sub-panel.

(((73)))
Phil Clements, K5PC


Re: Inrush filament current protection

FRANCIS CARCIA
 

I get along with my guy very well for the reasons you stated. Life is short and best to get the inspector out of it ASAP.

"Robert B. Bonner" wrote:

Yeah some of these guys interpret the code differently Have their own
opinions. Thats why there are lawyers and judges, hahahaha

My local inspector considered the water pipe as the real ground The ground
rods as a supplementary ground.

While this is incorrect it is supposed to be the other way around by
definition.

The water pipes in his argument are better grounded than the ground rod

The correct answers when dealing with ANY INSPECTOR are YES SIR and OK
thats good to know, hahahaha.

BOB DD

________________________________________
From: ham_amplifiers@yahoogroups.com [mailto:ham_amplifiers@yahoogroups.com]
On Behalf Of FRANCIS CARCIA
Sent: Monday, November 13, 2006 12:01 PM
To: ham_amplifiers@yahoogroups.com
Subject: RE: [ham_amplifiers] Re: Inrush filament current protection

My building inspector did not want the ground wire in the meter socket. I
ran conduit off the breaker panel to the rods. I also ran #4 over to the
water main both sides of the meter. Then I showed him?the 4 #8s coming
through the wall that go around the footing and through the yard. He smiled
and said connect them also. Next I got some interesting lightning stories.
gfz

"Robert B. Bonner" <rbonner@qro.com> wrote:

-----Original Message-----
From: ham_amplifiers@yahoogroups.com [mailto:ham_amplifiers@yahoogroups.com]
On Behalf Of R L Measures
Sent: Monday, November 13, 2006 9:41 AM
To: ham_amplifiers@yahoogroups.com
Subject: Re: [ham_amplifiers] Re: Inrush filament current protection

On Nov 13, 2006, at 4:48 AM, Robert B. Bonner wrote:

> Jim,
>
> I know several years ago a friend sent me some copies of the posts
> on AMPS
> when I wasn't a member. There were comments rather heated regarding
> POWER
> SERVICES and AC wiring to amps.
>
> I will end that quickly here as I won't tolerate incorrect info to
> pass me
> by. You are a smart guy, very knowledgeable and have some good
> experiences
> but let's define power services / wiring correctly to avoid any
> errors.
>
> You and I are saying the same things but differently. Separated by
> a common
> language.
>
> I worked three years as an electrician... Knew my business.
>
> Standard 220V

Is not 240v standard in the United States?

*** You can call it whatever you want, there is no actual voltage
220-230-234-240.. So you will sometimes see it referenced 220/240 which is
the correct term.

Or my favorite inside electrician's joke "220-221 whatever it takes" (From
the movie Mr. Mom) It's a range power companies try to maintain between
approximately 220 and 240 volts.

(My second favorite electrician's joke is what do you need to know to be a
plumber? Answer: S*** flows downhill and payday is Friday...)

Mine runs almost 250 volts here most times. Just checked it it is 246.5
VRMS right now.

> residential circuits are two wire, the third wire is a GROUND
> (Green) not a neutral.

If they connect together in the breaker box, is this really safe?
... ...

*** Ask the guys who write the national electric code. I am but their local
servant. :-)

Ground should be ground... The equipment connected and the service entrance
should all be grounded. My original power service in this house 42 years
ago was grounded to water pipes. Then "they" also found that water
companies would remove water meters from time to time, so now it is required
by code to jumper over the water meter to maintain ground during that
service. Lost a few meter technicians over time I suppose.

Plus now current code requires at the meter socket you have quantity two
5/8" 8 foot copper ground rods 6' apart outside grounding the meter socket.
Plus if you use non-metallic conduit between the panel and meter socket you
need to pull a ground wire through there.

"They" (The Power Gods) want NEUTRAL which is provided by the power company
to be kept as close to ground potential as possible. The power company does
not provide you a GROUND, They don't provide you technically 220/240 either,
they provide two circuits of out of phase 120 on either side of a neutral;
it is your responsibility to provide the GROUND and quite if by magic you
make 240 Volts inside your panel.

Consumers make all sorts of assumptions... Where actually as the consumer
you are making the various voltages to power your house by yourself.

You provide the ground... Which is the return path for the power company's
7200 Volts. (They only ground every other pole usually) and You make
220/240 inside your panel by wiring the out of phase 120's together.

If you look at it that way... With Joe ham wiring away in his box not
understanding what's actually going on, How safe is that? Maybe Europe's
250 scenario is a lot safer to start with?

The bonding strap in a power panel is about a 10 gauge aluminum strap is
all. Which is adequate if you don't ask ground to carry any current from
gear. I have never heard of one of those melting in half except after a
lightning strike, but it could happen if you drew power acrossed it.

BOB DD

R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org

Yahoo! Groups Links



Re: Inrush filament current protection

Robert B. Bonner
 

Yeah some of these guys interpret the code differently… Have their own
opinions. That’s why there are lawyers and judges, hahahaha

My local inspector considered the water pipe as the real ground… The ground
rods as a supplementary ground.

While this is incorrect it is supposed to be the other way around by
definition.

The water pipes in his argument are better grounded than the ground rod…

The correct answers when dealing with ANY INSPECTOR are YES SIR and OK
that’s good to know, hahahaha.

BOB DD

________________________________________
From: ham_amplifiers@... [mailto:ham_amplifiers@...]
On Behalf Of FRANCIS CARCIA
Sent: Monday, November 13, 2006 12:01 PM
To: ham_amplifiers@...
Subject: RE: [ham_amplifiers] Re: Inrush filament current protection

My building inspector did not want the ground wire in the meter socket. I
ran conduit off the breaker panel to the rods. I also ran #4 over to the
water main both sides of the meter. Then I showed him?the 4 #8s coming
through the wall that go around the footing and through the yard. He smiled
and said connect them also. Next I got some interesting lightning stories.
gfz

"Robert B. Bonner" <rbonner@...> wrote:

-----Original Message-----
From: ham_amplifiers@... [mailto:ham_amplifiers@...]
On Behalf Of R L Measures
Sent: Monday, November 13, 2006 9:41 AM
To: ham_amplifiers@...
Subject: Re: [ham_amplifiers] Re: Inrush filament current protection

On Nov 13, 2006, at 4:48 AM, Robert B. Bonner wrote:

Jim,

I know several years ago a friend sent me some copies of the posts
on AMPS
when I wasn't a member. There were comments rather heated regarding
POWER
SERVICES and AC wiring to amps.

I will end that quickly here as I won't tolerate incorrect info to
pass me
by. You are a smart guy, very knowledgeable and have some good
experiences
but let's define power services / wiring correctly to avoid any
errors.

You and I are saying the same things but differently. Separated by
a common
language.

I worked three years as an electrician... Knew my business.

Standard 220V
Is not 240v standard in the United States?

*** You can call it whatever you want, there is no actual voltage
220-230-234-240.. So you will sometimes see it referenced 220/240 which is
the correct term.

Or my favorite inside electrician's joke "220-221 whatever it takes" (From
the movie Mr. Mom) It's a range power companies try to maintain between
approximately 220 and 240 volts.

(My second favorite electrician's joke is what do you need to know to be a
plumber? Answer: S*** flows downhill and payday is Friday...)

Mine runs almost 250 volts here most times. Just checked it it is 246.5
VRMS right now.

residential circuits are two wire, the third wire is a GROUND
(Green) not a neutral.
If they connect together in the breaker box, is this really safe?
... ...

*** Ask the guys who write the national electric code. I am but their local
servant. :-)

Ground should be ground... The equipment connected and the service entrance
should all be grounded. My original power service in this house 42 years
ago was grounded to water pipes. Then "they" also found that water
companies would remove water meters from time to time, so now it is required
by code to jumper over the water meter to maintain ground during that
service. Lost a few meter technicians over time I suppose.

Plus now current code requires at the meter socket you have quantity two
5/8" 8 foot copper ground rods 6' apart outside grounding the meter socket.
Plus if you use non-metallic conduit between the panel and meter socket you
need to pull a ground wire through there.

"They" (The Power Gods) want NEUTRAL which is provided by the power company
to be kept as close to ground potential as possible. The power company does
not provide you a GROUND, They don't provide you technically 220/240 either,
they provide two circuits of out of phase 120 on either side of a neutral;
it is your responsibility to provide the GROUND and quite if by magic you
make 240 Volts inside your panel.

Consumers make all sorts of assumptions... Where actually as the consumer
you are making the various voltages to power your house by yourself.

You provide the ground... Which is the return path for the power company's
7200 Volts. (They only ground every other pole usually) and You make
220/240 inside your panel by wiring the out of phase 120's together.

If you look at it that way... With Joe ham wiring away in his box not
understanding what's actually going on, How safe is that? Maybe Europe's
250 scenario is a lot safer to start with?

The bonding strap in a power panel is about a 10 gauge aluminum strap is
all. Which is adequate if you don't ask ground to carry any current from
gear. I have never heard of one of those melting in half except after a
lightning strike, but it could happen if you drew power acrossed it.

BOB DD

R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org

Yahoo! Groups Links


Re: Inrush filament current protection

Robert B. Bonner
 

See below

________________________________________
From: ham_amplifiers@... [mailto:ham_amplifiers@...]
On Behalf Of KR4DA
Sent: Monday, November 13, 2006 10:31 AM
To: ham_amplifiers@...
Subject: Re: [ham_amplifiers] Re: Inrush filament current protection

210-250v depends on the utility company...
My experience and I am not certified....
read any basic book on it.....
I have done most of the wiring around my house.. a well
and the pool and the 24x30 shop with welders etc.....
up to 220v is not rocket science..
Should be four wires.
1. RED 120v one phase side
2.BLACK 120v one phase side
3. WHITE neutral
4.plain copper wire.


**** Red and Black are both acceptable colors to use, they don't have to be
one red and one black. You should be very careful if you get into 3 phase
at all as they become different meanings.

When in YES you can use the WHITE 120v BLACK 120v and the plain
copper wire as GND. But you might confuse a person thinking
this is a 110v wiring as white is NOT supposed to have 110v on it...
WHITE is supposed to be NEUTRAL.

**** You can pull a standard Romex line with white - black and bare ground
wire, however where the white is exposed YOU MUST cover the white with Black
tape to TELL SERVICE PEOPLE that this is the other leg of a 220/240 circuit.
This is allowed.

I do know they there is a chassis connection and a ground connection
on some electorical devices where this is need I am not sure.
I have seen some old TUBE stuff that required this.

Usually the white and plain copper are connected together at the BOX.
BUT the white has one bus bar and the plain copper has another.
If you look in the power box the power company neutral is tied to a COMMAN
BAR this is where the WHITES are connected... BUT then running from the
power company neutral is usually another BAR going to a strip where the
plain copper wires are attached.
There is no actual really separation on these GND and neutral bars...
It's a just do it this way thing.

**** Yes you are correct there are separate busses in the panel. This is
because neutral and ground are not supposed to be the same thing, however
they are tied together. NEVER confuse them as the same thing as they are
never the SAME even if they appear to be tied together. The white wire is a
current carrying conductor and the green or bare is not. Is this over kill?
Not if it saves your life.

This is done to standardize power panels. Sure as S*** somebody here is
going to pop a cover off a 3 phase panel someday and kill himself if he
doesn't learn what things are and why...

When you get into HIGHER more complicated phases of power 440 880v then the
GND and NEUTRAL provided by the power company are critical.
But not for 220v requirements.

Incorrect, but this is the Consumer fallacy I'm trying to cure.

*** Remember I've already said the power company doesn't provide GROUND you
do.

Its like GUNS don't kill people - People kill people..

While you can justify "They are all the Same" this is a poor justification.
The rules of electricity are developed to kill as few people a year as
possible. When you start treating things the same is when you will become a
statistic.

Let's respect the CORRECT definitions and uses of these conductors. (Whether
I can convince you they are different or not)

Some day your whole house will be full of ARC FAULT and GROUND FAULT
Breakers. They are now becoming code... When that day comes you'll be in a
world of hurt otherwise.

BOB DD

AKA "Electro the Magnificent" I didn't make that up BTW, I was dubbed that
by a past employer. OH yeah and if you want a violent code argument I'll
give you Don "The CODE" Coder's phone number he even drove me nuts with code
discussions, I'm a pussy cat in comparison... :-) RB BWAAAHAHAHAHAHA!

R L Measures wrote:


On Nov 13, 2006, at 4:48 AM, Robert B. Bonner wrote:

Jim,

I know several years ago a friend sent me some copies of the posts
on AMPS
when I wasn't a member. There were comments rather heated regarding
POWER
SERVICES and AC wiring to amps.

I will end that quickly here as I won't tolerate incorrect info to
pass me
by. You are a smart guy, very knowledgeable and have some good
experiences
but let's define power services / wiring correctly to avoid any
errors.

You and I are saying the same things but differently. Separated by
a common
language.

I worked three years as an electrician... Knew my business.

Standard 220V
Is not 240v standard in the United States?
residential circuits are two wire, the third wire is a GROUND
(Green) not a neutral.
If they connect together in the breaker box, is this really safe?
... ...
R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


--
de KR4DA Bob Middleburg, FL
HK0/KR4DA J79DA FG/KR4DA


Re: Inrush filament current protection

 

On Nov 13, 2006, at 8:30 AM, KR4DA wrote:

210-250v depends on the utility company...
Not in California, it's set at 228v to 240v by the PUC.
My experience and I am not certified....
read any basic book on it.....
I do not believe everything in any book.
I have done most of the wiring around my house.. a well
and the pool and the 24x30 shop with welders etc.....
up to 220v is not rocket science..
Should be four wires.
1. RED 120v one phase side 2.BLACK 120v one phase side
3. WHITE neutral 4.plain copper wire.
When in YES you can use the WHITE 120v BLACK 120v and the plain
copper wire as GND. But you might confuse a person thinking
this is a 110v wiring as white is NOT supposed to have 110v on it...
WHITE is supposed to be NEUTRAL.
I do know they there is a chassis connection and a ground connection
on some electorical devices where this is need I am not sure.
I have seen some old TUBE stuff that required this.


Usually the white and plain copper are connected together at the BOX.
It's required in this neck of the woods.

BUT the white has one bus bar and the plain copper has another.
If you look in the power box the power company neutral is tied to a COMMAN
BAR this is where the WHITES are connected... BUT then running from the
power company neutral is usually another BAR going to a strip where the plain copper wires are attached.
I looked. In our breaker box, all the ground wires and all the Neutral wire connecct in one bus bar. How would it be different if there were two bus bars that are connected by a bus-wire?
...
cheers, Bob
R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


Re: NOS cermic-metal tube burn in

 

What is the screen PS V?
What is the anode PS V?

What Class?

On Nov 13, 2006, at 7:34 AM, Hsu wrote:

Hi, There are two Chinese FU-251F(4CX250B) cermic-metal tubes, they are new but storge for very long time. The output power only 200-250W( a pair), Could someone cal tell me how to solve this problem?Is it means I have to drop them in the junk box?
73! Hsu

R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


Re: Inrush filament current protection

FRANCIS CARCIA
 

My building inspector did not want the ground wire in the meter socket. I ran conduit off the breaker panel to the rods. I also ran #4 over to the water main both sides of the meter. Then I showed him?the 4 #8s coming through the wall that go around the footing and through the yard. He smiled and said connect them also. Next I got some interesting lightning stories. gfz

"Robert B. Bonner" wrote:



-----Original Message-----
From: ham_amplifiers@yahoogroups.com [mailto:ham_amplifiers@yahoogroups.com]
On Behalf Of R L Measures
Sent: Monday, November 13, 2006 9:41 AM
To: ham_amplifiers@yahoogroups.com
Subject: Re: [ham_amplifiers] Re: Inrush filament current protection

On Nov 13, 2006, at 4:48 AM, Robert B. Bonner wrote:

> Jim,
>
> I know several years ago a friend sent me some copies of the posts
> on AMPS
> when I wasn't a member. There were comments rather heated regarding
> POWER
> SERVICES and AC wiring to amps.
>
> I will end that quickly here as I won't tolerate incorrect info to
> pass me
> by. You are a smart guy, very knowledgeable and have some good
> experiences
> but let's define power services / wiring correctly to avoid any
> errors.
>
> You and I are saying the same things but differently. Separated by
> a common
> language.
>
> I worked three years as an electrician... Knew my business.
>
> Standard 220V

Is not 240v standard in the United States?

*** You can call it whatever you want, there is no actual voltage
220-230-234-240.. So you will sometimes see it referenced 220/240 which is
the correct term.

Or my favorite inside electrician's joke "220-221 whatever it takes" (From
the movie Mr. Mom) It's a range power companies try to maintain between
approximately 220 and 240 volts.

(My second favorite electrician's joke is what do you need to know to be a
plumber? Answer: S*** flows downhill and payday is Friday...)

Mine runs almost 250 volts here most times. Just checked it it is 246.5
VRMS right now.

> residential circuits are two wire, the third wire is a GROUND
> (Green) not a neutral.

If they connect together in the breaker box, is this really safe?
... ...

*** Ask the guys who write the national electric code. I am but their local
servant. :-)

Ground should be ground... The equipment connected and the service entrance
should all be grounded. My original power service in this house 42 years
ago was grounded to water pipes. Then "they" also found that water
companies would remove water meters from time to time, so now it is required
by code to jumper over the water meter to maintain ground during that
service. Lost a few meter technicians over time I suppose.

Plus now current code requires at the meter socket you have quantity two
5/8" 8 foot copper ground rods 6' apart outside grounding the meter socket.
Plus if you use non-metallic conduit between the panel and meter socket you
need to pull a ground wire through there.

"They" (The Power Gods) want NEUTRAL which is provided by the power company
to be kept as close to ground potential as possible. The power company does
not provide you a GROUND, They don't provide you technically 220/240 either,
they provide two circuits of out of phase 120 on either side of a neutral;
it is your responsibility to provide the GROUND and quite if by magic you
make 240 Volts inside your panel.

Consumers make all sorts of assumptions... Where actually as the consumer
you are making the various voltages to power your house by yourself.

You provide the ground... Which is the return path for the power company's
7200 Volts. (They only ground every other pole usually) and You make
220/240 inside your panel by wiring the out of phase 120's together.

If you look at it that way... With Joe ham wiring away in his box not
understanding what's actually going on, How safe is that? Maybe Europe's
250 scenario is a lot safer to start with?

The bonding strap in a power panel is about a 10 gauge aluminum strap is
all. Which is adequate if you don't ask ground to carry any current from
gear. I have never heard of one of those melting in half except after a
lightning strike, but it could happen if you drew power acrossed it.

BOB DD

R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org

Yahoo! Groups Links



Re: Inrush filament current protection

Robert B. Bonner
 

-----Original Message-----
From: ham_amplifiers@... [mailto:ham_amplifiers@...]
On Behalf Of R L Measures
Sent: Monday, November 13, 2006 9:41 AM
To: ham_amplifiers@...
Subject: Re: [ham_amplifiers] Re: Inrush filament current protection


On Nov 13, 2006, at 4:48 AM, Robert B. Bonner wrote:

Jim,

I know several years ago a friend sent me some copies of the posts
on AMPS
when I wasn't a member. There were comments rather heated regarding
POWER
SERVICES and AC wiring to amps.

I will end that quickly here as I won't tolerate incorrect info to
pass me
by. You are a smart guy, very knowledgeable and have some good
experiences
but let's define power services / wiring correctly to avoid any
errors.

You and I are saying the same things but differently. Separated by
a common
language.

I worked three years as an electrician... Knew my business.

Standard 220V
Is not 240v standard in the United States?

*** You can call it whatever you want, there is no actual voltage
220-230-234-240.. So you will sometimes see it referenced 220/240 which is
the correct term.

Or my favorite inside electrician's joke "220-221 whatever it takes" (From
the movie Mr. Mom) It's a range power companies try to maintain between
approximately 220 and 240 volts.

(My second favorite electrician's joke is what do you need to know to be a
plumber? Answer: S*** flows downhill and payday is Friday...)

Mine runs almost 250 volts here most times. Just checked it it is 246.5
VRMS right now.

residential circuits are two wire, the third wire is a GROUND
(Green) not a neutral.
If they connect together in the breaker box, is this really safe?
... ...

*** Ask the guys who write the national electric code. I am but their local
servant. :-)

Ground should be ground... The equipment connected and the service entrance
should all be grounded. My original power service in this house 42 years
ago was grounded to water pipes. Then "they" also found that water
companies would remove water meters from time to time, so now it is required
by code to jumper over the water meter to maintain ground during that
service. Lost a few meter technicians over time I suppose.

Plus now current code requires at the meter socket you have quantity two
5/8" 8 foot copper ground rods 6' apart outside grounding the meter socket.
Plus if you use non-metallic conduit between the panel and meter socket you
need to pull a ground wire through there.

"They" (The Power Gods) want NEUTRAL which is provided by the power company
to be kept as close to ground potential as possible. The power company does
not provide you a GROUND, They don't provide you technically 220/240 either,
they provide two circuits of out of phase 120 on either side of a neutral;
it is your responsibility to provide the GROUND and quite if by magic you
make 240 Volts inside your panel.

Consumers make all sorts of assumptions... Where actually as the consumer
you are making the various voltages to power your house by yourself.

You provide the ground... Which is the return path for the power company's
7200 Volts. (They only ground every other pole usually) and You make
220/240 inside your panel by wiring the out of phase 120's together.

If you look at it that way... With Joe ham wiring away in his box not
understanding what's actually going on, How safe is that? Maybe Europe's
250 scenario is a lot safer to start with?

The bonding strap in a power panel is about a 10 gauge aluminum strap is
all. Which is adequate if you don't ask ground to carry any current from
gear. I have never heard of one of those melting in half except after a
lightning strike, but it could happen if you drew power acrossed it.

BOB DD

R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org






Yahoo! Groups Links


Re: 3-500Z socket.... Johnson vs Eimac

Peter Voelpel
 

Rich,

it says 0.082" at sea level and 500W dissipation

73
Peter

-----Original Message-----

The Eimac spec sheet says 0.82" at sea level.
And that's for 500/1000 w CCS
anode diss. Now .13" pressure is zip imo.


Re: Inrush filament current protection

KR4DA
 

开云体育

210-250v depends on the utility company...
My experience and I am not certified....
read any basic book on it.....
I have done most of the wiring around my house.. a well
and the pool and the 24x30 shop with welders etc.....
up to 220v is not rocket science..
Should be four wires.
1. RED 120v one phase side 2.BLACK 120v one phase side
3. WHITE neutral 4.plain copper wire.
When in YES you can use the WHITE 120v BLACK 120v and the plain
copper wire as GND. But you might confuse a person thinking
this is a 110v wiring as white is NOT supposed to have 110v on it...
WHITE is supposed to be NEUTRAL.
I do know they there is a chassis connection and a ground connection
on some electorical devices where this is need I am not sure.
I have seen some old TUBE stuff that required this.


Usually the white and plain copper are connected together at the BOX.
BUT the white has one bus bar and the plain copper has another.
If you look in the power box the power company neutral is tied to a COMMAN
BAR this is where the WHITES are connected... BUT then running from the
power company neutral is usually another BAR going to a strip where the plain copper wires are attached.
There is no actual really separation on these GND and neutral bars...
It's a just do it this way thing.

When you get into HIGHER more complicated phases of power 440 880v then the
GND and NEUTRAL provided by the power company are critical.
But not for 220v requirements.




R L Measures wrote:


On Nov 13, 2006, at 4:48 AM, Robert B. Bonner wrote:

> Jim,
>
> I know several years ago a friend sent me some copies of the posts
> on AMPS
> when I wasn't a member. There were comments rather heated regarding
> POWER
> SERVICES and AC wiring to amps.
>
> I will end that quickly here as I won't tolerate incorrect info to
> pass me
> by. You are a smart guy, very knowledgeable and have some good
> experiences
> but let's define power services / wiring correctly to avoid any
> errors.
>
> You and I are saying the same things but differently. Separated by
> a common
> language.
>
> I worked three years as an electrician... Knew my business.
>
> Standard 220V

Is not 240v standard in the United States?
> residential circuits are two wire, the third wire is a GROUND
> (Green) not a neutral.

If they connect together in the breaker box, is this really safe?
... ...
>

R L Measures, AG6K, 805.386.3734
r@..., rlm@...,


-- 
de KR4DA Bob Middleburg, FL
HK0/KR4DA J79DA FG/KR4DA


Re: 3-500Z socket.... Johnson vs Eimac

 

On Nov 13, 2006, at 2:30 AM, pentalab wrote:

--- In ham_amplifiers@..., R L Measures <r@...> wrote:

RICH SEZ... The problem is that the 3-500Z air system socket
requires a high-pressure centrifugal blower, and Ham amps used an
ordinary centrifugal blower.

### See my note above. A 3-500Z only requires a .08" h2o
pressure.

RICH SEZ... Correct, but Eimac's 0.82" water column spec is the
pressure differential across the socket, and that usually means a
fairly noisy blower.

### The actual spec for a 3-500Z is 13 cfm @ .13" h2o...... or
26 cfm @ .13"... for a pair.
The Eimac spec sheet says 0.82" at sea level.
And that's for 500/1000 w CCS
anode diss. Now .13" pressure is zip imo.
Opinions count way less than manometer measurements.
Heck......

RICH SEZ... That's how I do it. I also use a varnished cardboard
flap that hinges up to let the air out. It just doesn't look as
pretty.

### It would look like hell! Now that's what I call "K-mart
construction". Rich would call it part of his.. "ugly amplifier"
scene.
A square of varnished cardboard with two nickels glued to the
corners along one edge is light enough to rise automatically with
the airflow passing through an 8170. When the amp is off the
cardboard flops down, keeping spiders from constructing webs on the
insides.

### well, at least you got 2 x nickels to rub together !
The nickels are glued down about 5" apart.

### here's the interesting bit. Eimac states the glass tubes
cool by infared radiation.... well my natural gas fireplace puts
out loads of radiant heat.... a 3-500Z doesn't.
RICH SEZ... So objects that glow red-orange do not exhibit infra-
red radiation?

### If a 3-500Z is suppose to cool partially via infrared
radiation... I think they are full of it.
They are correct -- it's called Stephan's Law and the power radiated
is a function of the object's Temp raised to the 4th power.

I can put my hands
You would have done somewhat better at this point had you put your
hands on the mouse and clicked Send. .
on the
left side cabinet... [which is flat black... in and out]... and it's
stone cold... and also has zero air on it. You can take the cab
right off... and put ur hand [carefully] on the insides anywhere...
and feel no heat from the infrared radiation. The outsides of the
chimney's are hot [dead cxr, tubes red]... but that's from a lack
of air. The puny blower in the L4B is good for 600W CCS anode
diss... NOT 1kw. The point is.. the infrared radiation is not
heating anything else up in the cabinet. The Fluke 62 IR confirms
this.

### Another point here. The 3CX-800A7 has got 60% MORE anode
diss than a 3-500Z.... but only requires 46% more CFM than a 3-
500Z. So much for..."cooling" by infrared radiation.

### Rich... if you operated the SB-220 at 1500W out RTTY for 1
hr... you wouldn't have enough cooling on the tubes.
The SB-220 has a ≈600W HV transformer. Hello!
cheers, Jim
.

R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


Re: "Father Measures"

 

On Nov 13, 2006, at 3:53 AM, pentalab wrote:

--- In ham_amplifiers@..., R L Measures <r@...> wrote:

RICH SEZ... Amen, however, some of my friends have told me I would
make a good priest. Maybe they were joking?...

### I can just see it now.... "Father Measures" ... up on the mound..
preaching a fire and brimstone lecture about..."parasitic hell"....to
us globar heathen's, with the ARRL bible in one hand.... and a wouf
hong ...made of solid Nichrome in the other hand. Quick... run for
your lives ! The sky is falling.
Hardly, Jim. I know too much about history to ever join any organized religion.

cheers

later... Jim VE7RF
... ...

.

R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


Re: Inrush filament current protection

 

On Nov 13, 2006, at 4:48 AM, Robert B. Bonner wrote:

Jim,

I know several years ago a friend sent me some copies of the posts on AMPS
when I wasn't a member. There were comments rather heated regarding POWER
SERVICES and AC wiring to amps.

I will end that quickly here as I won't tolerate incorrect info to pass me
by. You are a smart guy, very knowledgeable and have some good experiences
but let's define power services / wiring correctly to avoid any errors.

You and I are saying the same things but differently. Separated by a common
language.

I worked three years as an electrician... Knew my business.

Standard 220V
Is not 240v standard in the United States?
residential circuits are two wire, the third wire is a GROUND
(Green) not a neutral.
If they connect together in the breaker box, is this really safe?
... ...
R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


NOS cermic-metal tube burn in

Hsu
 

Hi, There are two Chinese FU-251F(4CX250B) cermic-metal tubes, they are new but storge for very long time. The output power only 200-250W( a pair), Could someone cal tell me how to solve this problem?Is it means I have to drop them in the junk box?
73! Hsu