Re: [ExternalEmail] Re: [4x6bandsaw] motor acted funny the other day


 

A three-phase motor overload will not properly protect a single-phase motor if you use only one pole. The overload units are calibrated for current in all three poles. You can use it if you daisy chain all three poles together or some combination of neutral and phase so that all the poles have current. Otherwise, the overload will operate at a much higher current because they will not see mutual heating from the adjacent poles. See:

?

?


On Thu, Jan 2, 2020 at 8:40 AM Jim.Klessig@... <jim.klessig@...> wrote:
¡°is there any way that a 'NEMA motor starter with properly selected heater ' can be retrofitted to our 1/3 or 1/2 HP motors??¡°
?
Yes, you can buy a brand new Nema size 00 Motor starter for single phase motors.
? They are NOT however cheap.
?
Expect to pay anywhere from $70 to $300.
?
You can also use an appropriately sized 3 phase one, just using a single phase of the unit.
?
A motor starter consists of a Contactor (really a heavy duty relay) that does the switching,
and an overload relay, that senses the current, and some controls.
These can be added to any motor. They are completely external to them.
You nit the start button, that energizes the contactor, which seals in, and the motor starts,
when the OL relay sees too much current for too long, it opens the seal in circuit, and the contactor opens.
?
The motors with built in protection have a device built in to the windings that acts (sort of)
as the relay and contactor combined. They actually provide better protection (since they sense
the ACTUAL temperature of the motor winding, rather than a guess at it) but are not as durable (IMO).
?
In EITHER case, NEITHER provide short circuit protection, so you need that in your circuit as well.
(but it is probably there already)
?
?
?
OUR EMAIL ADDRESSES HAVE CHANGED
We were xxxxx@vertivCO.com and we are now xxxxx@...
?
?
R James (Jim) Klessig P.E. | Senior Power Systems Engineer |
Electrical Reliability Services, VERTIV
jim.klessig@..., jim_klessig@...
1876 Gwin Rd, Mckinleyville | CA | 95519 | USA
| Cell (707) 497-9611 | eFax 614-410-0653
?
?
CONFIDENTIALITY NOTICE: This e-mail and any files transmitted with it are intended solely for the use of the individual or entity to whom they are addressed and may contain confidential and privileged information protected by law. If you received this e-mail in error, any review, use, dissemination, distribution, or copying of the e-mail is strictly prohibited. Please notify the sender immediately by return e-mail and delete all copies from your system.



--
John A. Schirra?
Sent from GMail

Join [email protected] to automatically receive all group messages.