¿ªÔÆÌåÓý

ctrl + shift + ? for shortcuts
© 2025 Groups.io
Date

Re: 3-500Z socket.... Johnson vs Eimac

 

On Nov 13, 2006, at 2:30 AM, pentalab wrote:

--- In ham_amplifiers@..., R L Measures <r@...> wrote:

RICH SEZ... The problem is that the 3-500Z air system socket
requires a high-pressure centrifugal blower, and Ham amps used an
ordinary centrifugal blower.

### See my note above. A 3-500Z only requires a .08" h2o
pressure.

RICH SEZ... Correct, but Eimac's 0.82" water column spec is the
pressure differential across the socket, and that usually means a
fairly noisy blower.

### The actual spec for a 3-500Z is 13 cfm @ .13" h2o...... or
26 cfm @ .13"... for a pair.
The Eimac spec sheet says 0.82" at sea level.
And that's for 500/1000 w CCS
anode diss. Now .13" pressure is zip imo.
Opinions count way less than manometer measurements.
Heck......

RICH SEZ... That's how I do it. I also use a varnished cardboard
flap that hinges up to let the air out. It just doesn't look as
pretty.

### It would look like hell! Now that's what I call "K-mart
construction". Rich would call it part of his.. "ugly amplifier"
scene.
A square of varnished cardboard with two nickels glued to the
corners along one edge is light enough to rise automatically with
the airflow passing through an 8170. When the amp is off the
cardboard flops down, keeping spiders from constructing webs on the
insides.

### well, at least you got 2 x nickels to rub together !
The nickels are glued down about 5" apart.

### here's the interesting bit. Eimac states the glass tubes
cool by infared radiation.... well my natural gas fireplace puts
out loads of radiant heat.... a 3-500Z doesn't.
RICH SEZ... So objects that glow red-orange do not exhibit infra-
red radiation?

### If a 3-500Z is suppose to cool partially via infrared
radiation... I think they are full of it.
They are correct -- it's called Stephan's Law and the power radiated
is a function of the object's Temp raised to the 4th power.

I can put my hands
You would have done somewhat better at this point had you put your
hands on the mouse and clicked Send. .
on the
left side cabinet... [which is flat black... in and out]... and it's
stone cold... and also has zero air on it. You can take the cab
right off... and put ur hand [carefully] on the insides anywhere...
and feel no heat from the infrared radiation. The outsides of the
chimney's are hot [dead cxr, tubes red]... but that's from a lack
of air. The puny blower in the L4B is good for 600W CCS anode
diss... NOT 1kw. The point is.. the infrared radiation is not
heating anything else up in the cabinet. The Fluke 62 IR confirms
this.

### Another point here. The 3CX-800A7 has got 60% MORE anode
diss than a 3-500Z.... but only requires 46% more CFM than a 3-
500Z. So much for..."cooling" by infrared radiation.

### Rich... if you operated the SB-220 at 1500W out RTTY for 1
hr... you wouldn't have enough cooling on the tubes.
The SB-220 has a ¡Ö600W HV transformer. Hello!
cheers, Jim
.

R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


Re: "Father Measures"

 

On Nov 13, 2006, at 3:53 AM, pentalab wrote:

--- In ham_amplifiers@..., R L Measures <r@...> wrote:

RICH SEZ... Amen, however, some of my friends have told me I would
make a good priest. Maybe they were joking?...

### I can just see it now.... "Father Measures" ... up on the mound..
preaching a fire and brimstone lecture about..."parasitic hell"....to
us globar heathen's, with the ARRL bible in one hand.... and a wouf
hong ...made of solid Nichrome in the other hand. Quick... run for
your lives ! The sky is falling.
Hardly, Jim. I know too much about history to ever join any organized religion.

cheers

later... Jim VE7RF
... ...

.

R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


Re: Inrush filament current protection

 

On Nov 13, 2006, at 4:48 AM, Robert B. Bonner wrote:

Jim,

I know several years ago a friend sent me some copies of the posts on AMPS
when I wasn't a member. There were comments rather heated regarding POWER
SERVICES and AC wiring to amps.

I will end that quickly here as I won't tolerate incorrect info to pass me
by. You are a smart guy, very knowledgeable and have some good experiences
but let's define power services / wiring correctly to avoid any errors.

You and I are saying the same things but differently. Separated by a common
language.

I worked three years as an electrician... Knew my business.

Standard 220V
Is not 240v standard in the United States?
residential circuits are two wire, the third wire is a GROUND
(Green) not a neutral.
If they connect together in the breaker box, is this really safe?
... ...
R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


NOS cermic-metal tube burn in

Hsu
 

Hi, There are two Chinese FU-251F(4CX250B) cermic-metal tubes, they are new but storge for very long time. The output power only 200-250W( a pair), Could someone cal tell me how to solve this problem?Is it means I have to drop them in the junk box?
73! Hsu


Re: Inrush filament current protection

Robert B. Bonner
 

Jim,

I know several years ago a friend sent me some copies of the posts on AMPS
when I wasn't a member. There were comments rather heated regarding POWER
SERVICES and AC wiring to amps.

I will end that quickly here as I won't tolerate incorrect info to pass me
by. You are a smart guy, very knowledgeable and have some good experiences
but let's define power services / wiring correctly to avoid any errors.

You and I are saying the same things but differently. Separated by a common
language.

I worked three years as an electrician... Knew my business.

Standard 220V residential circuits are two wire, the third wire is a GROUND
(Green) not a neutral.

Most dryers are 2 wires plus ground here. You wire your Ameritron its two
wires plus a ground.

If you have a 4 wire 220 circuit including Power Cord and a 4 conductor
plug... Two blacks a white and a green. You have 220 plus neutral. This
will give you 220V via two 120 circuits and a ground. This is a direct
extension of your panel service.

Most residential 220V items don't use 4 wire.

Not to be confused with 3 Phase which is all different colors / uses.

In residential services in the states we tie the NEUTRALS and the GROUND
Buss together in the main panels, however that NEVER by definition makes
them "the same thing". Neutral is Neutral and Ground is always Ground.

Try switching them in a ground fault circuit and the breaker will blow.

The green wire should NEVER conduct current. SO if you are utilizing a 120
volt transformer somewhere in your homebrew for a control circuit or
filament you should also be utilizing either a 220-120V step down
transformer in your construction or a 4 wire 220 circuit to meet code...

This is why large commercial HF power generators like the Henrys (even the
8K) have 220-120 step down transformers inside them.

Others use 220V filament transformers not 120 to meet the electrical code...

Why don't they use all 220 transformers? New regs requiring both legs to
blow when one goes. They put gangbared main breakers on the gear, but
utilize 120 volt fuses for all the other small circuits to save money. The
220-120 step down is cheaper to fuse than dual breakers on all circuits.

Now will it work your way? That is 120V circuits wired to one side of the
line? YES... Does it meet code? No...

FYI The base Alpha 77 wasn't UL approved. It had a hot ground wire. There
was a higher cost version that had a step down transformer in it if you
REQUIRED a two wire circuit. That's mentioned right in their manual.

You are correct on all the other points. The separate CB's wouldn't fly
today without a tied together gangbar to kill both sides of the AC line.

A Grandfathered in system does not make it a good system. :-(

That's what I was referring to as CHEATING The System. Breaking the
Electrical Code.

Since we are basically saying the same thing differently... We have no
argument.

BOB DD

-----Original Message-----
From: ham_amplifiers@... [mailto:ham_amplifiers@...]
On Behalf Of pentalab
Sent: Monday, November 13, 2006 3:41 AM
To: ham_amplifiers@...
Subject: [ham_amplifiers] Re: Inrush filament current protection

--- In ham_amplifiers@..., "Robert B. Bonner"
<rbonner@...> wrote:

Garry,

That is a great question. I have a couple projects going together
RIGHT NOW that had me thinking the same thing.

It depends on if you cheat or not.
### huh ? AS long as you have a relay/contactor/ ckt breaker that
opens OFF BOTH sides of the 240v line... anything beyond that is
a moot point...and legal. BEWARE... if using fuses on the
primary.... they HAVE to be 240 V rated... NOT 120 V rated.
Here's why. IF only one fuse in one leg of the primary blew
open... and the 2nd fuse in the other leg was intact....you could
end up in a situation where 120 v is fed to one side of the plate
xfmr primary.... where it will simply pass throught the typ .08 ohm
dc resistance primary... then back to the OUTPUT side of the blown
fuse.[call this leg #2] Meanwhile... on the INPUT side of the
blown fuse.... you still have 120 V [coming from leg #1.] The
potential difference across the blown fuse in leg #1 will
be ...240 V. IE: with EITHER fuse blown [but only one], you
will have 240 v across an open fuse.... so DON'T use 120 V rated
fuses in either leg of a 240 v LINE.

### ALSO BEWARE.... some amps like the L4B... use two SEPARATE
circuit breaker's... one per hot leg... and NO tie bar between
em. These are usually the type that resemble a 3agc fuse
holder.When these type of breakers open up... they extend outwards.


OK what does that mean? 220V wiring is 2 wire plus ground, not 2
wire plus neutral.

### partially agreed. ALL wire now comes with a bare or
insulated grnd...whether u want it or not. The grnd is NEVER
considered any more in the wire count. So, you either
ask/order 2 conductor wire.... OR 3 conductor wire. 2 x
conductor wire comes with a grnd... so total wires = 3. 3 x
conductor wire also comes with a grnd... so total wires = 4. IE:
you ask fo 3 x wire XXX ga.... u get a total of 4 x conductor's.




If you use legal by code 220/221V (whatever it takes) building
practices you could get by with only 1 resistor in the step start.

#### The electrical code will state on a 240 v circuit you will
require a TWO pole breaker..and/or a TWO pole relay/contactor...
to open off BOTH sides of the line. After that.. they could care
less if u install a 12.5 ohm resistor in EACH hot leg... or a 25 ohm
resistor in just ONE hot leg. Putting a resistor in both legs is
a waste of effort. It's total LOOP resistance we are concerned
with here.




If you cheat and have some 110 volt circuitry in the amplifier
like a filament transformer that runs on 110 you would want to have
2 resistors in the step start.

### Agreed. BUT.... on an amp like the L4B.. and 99% of em...
that have a SEPARATE fil xfmr.... the fil xfmr will ALWAYS have
it's own dual 120 v primary's.... which can be wired in parallel
for 120v... or in series for 240 V. The only exception to
this.. would be if in a condo with 208/120V wiring per suite.
You can then run 208 V into the plate xfmr [wired for 240V.. so u
end up with slightly less plate V].... and run 120 V to the fil
xfmr [wired for 120V... so fil gets correct V]

### IF, indeed one had a fil xfmr that ONLY ran on 120v.... then,
you would have to ensure that the hot leg feeding the fil xfmr..
came from the SAME side of the 240 v line.... as your single
step start resistor.... so when step started... you step start BOTH
the HV supply AND the fil xfmr... at the same time...from the same
source.



In this situation you would have current flow on the GROUND LEAD.
### No you wouldn't. That could only happen if one side of the
120V fil xfmr [or any other 120 v device] was tied directly to
the chassis.. instead of the neutral. That isn't going to happen..
since it's not allowed... would violate every electrical code in
North America. On a similar note... you NEVER bond the neutral to
the chassis.... that also violates every electrical code in NA.
The ONLY thing bonded to the chassis is the grnd wire. With any
shorts from either side of line to chassis... the grnd wire
handles the full fault current.

### On circuits which require a huge 240 V load... like a HV
supply... but only a tiny load for the 120 V load... like say a
120 V blower... some tiny xfmr's for a T/R supply, etc... then
it would be ok to use a smaller neutral.... as long as the neutral
could handle the entire fault current... IF a line to neutral
short occured. EG: 2 ga wire for each hot leg... and a 100 A
main breaker in panel... but only 6 ga wire for the neutral....
and also 6 ga wire for the grnd.



That's why professional grade equipment has a 220 - 110 step down
transformer on board.
### You see that in the Henry 8 k manual. They do that to run
the 120 v Dayton blower. In EU/UK... they don't use a 3 wire 220
v line. They only have 2 x wires from the pole pig... with 220 v
across em. One side of the line is bonded to earth ground... so
one leg is hot... the other leg is valled neutral. That way, they
only have to fuse the ONE hot leg... and any switches, relays,
etc, are only required to be single pole types... for the one hot
leg. As per the 8K... when you look up the Dayton blower part
number they spec in their parts list in their manual.... and cross
reference it to the Dayton blowers on Grainger's website... turns
out it's the 230 V version of the same blower... and in fact, the
240/120 V step down xfmr shown in the schematic and also the picture
drawings.... doesn't exist.

## Notice on 240 V clothes dryers... they always include a
neutral... to run the 120 V blower. Seems stupid to me. They
shoulda just used a 240v blower... and could have eliminated the
requirement for a neutral..... just like a 240 v hot water
tank.... none of which have a neutral... since the heating els run
on 240 V only.




Another option is 4 wire circuitry where you have 220
plus neutral and ground. What a pain with the outlets etc...
### what's the problem with the outlets ??? A 30 A dryer
outlet comes with 2 x hots, one neutral... one gound. A 40 A
stove is exactly the same thing. Ditto with 20 A circuits.




A guy should follow good construction practices. BUT for home
brewing does it really matter? NAW it will turn on and work.

### with HB HV supplies... you don't need an outlet. You just
hardwire the 2 ga wire directly to the line side input of the
front or rear panel mounted breaker. OR hardwire the 2 ga wire
directly to the jumbo contactor input..... either way... you still
have the breaker in the main panel that feeds this mess. You can
buy 75/100/150/200 A outlets... cost a small fortune. You don't
need em.... just hardwire the big wire in..... and when working on
the amp.... kill the breaker in the main panel. IF the HV
supply/amp needs to be rolled over to the bench... just
disconnect the 4x wires at the HV/amp end.




Just an FYI, I use a double resistor. It just happens to look
prettier, double pole relay, pair of resistors, double pole relay
all in line. Nice pretty yellow adjustable time delay relay.

### Here's what I do. I use 25 ohms in one leg only... and only
one contactor to short out the resistor. The kicker is.. I use a
pair of paralled 50 ohm resistor's to make up the 25 ohms ! If
one resistor ever opened up... the 2nd one [albeit 50 ohms] is
still in the circiut. That way... I can never shunt an open single
resistor with the step start contactor... and slam a huge load on
the diodes.... IE: no step start at all... which would be a
disaster with 100-200 uf C input filter. These large metal
finned resistor's you see made by DALE and other's, works
perfectly for the step start R. Just bolt it to metal chassis
anywhere. Cuz of our magnetizing current.... I use a min of a 100w -
200 W rated units... EACH. You will have the entire 240 V
dumped across em when you 1st hit the switch. When everything
settles down... I still have 2 A of magnetizing current flowing
through em..[100/200 w]... then they get shunted.

## I also use the yellow /white adjustable Time delay relay. The
TD relays are all DPDT 10 A contacts.... which are used to
activate the coil of the step start contactor. The big step
start contactor has loads of AUX contacts... which are wired to
the amp key line.... ditto with main incoming contactor.... so
you can't key the amp unless all the contactor's are actually
operated. We use loads of 120 v neons as well.. status lamps...
to tell us instantly, where a problem is.. works slick.. if and when
it comes time to trbl shoot anything. A row of 3agc fuses [and
more neons on the output sides of the fuses] are the various feeds
for the blower, TD relays, small xfmr's for T/R relays, contactor's
etc.

### On the big stuff.... we use a separate Time delay for the fil
xfmr... which has it's own step start resistor/ variac, etc. The
fil TD is set for 8-10 seconds.... the HV delay is set for 15-
25 seconds. The blower over run TD is set for 15 mins.

-also have an airflow vane/ switch, retrofitted inside the blower.
Contacts of the airflow switch are wired to the coil of a small
relay.... whose contacts open off the 240 V to the fil xfmr.
The last thing you want is no air to a tube... esp when it's 30'
away... in another room. The slick thing about this setup is...
IF the commercial AC power goes off.... everything shuts down.
When the power comes back on.... everything just goes through it's
normal step start sequence etc. You can't key the amp... until
it's all finished.

Later... Jim VE7RF

BOB DD

-----Original Message-----
From: ham_amplifiers@...
[mailto:ham_amplifiers@...]
On Behalf Of Garry Drummond
Sent: Sunday, November 12, 2006 9:29 AM
To: ham_amplifiers@...
Subject: [ham_amplifiers] Inrush filament current protection

When running an amp on 240 volts, is it necessary to put a
resistor in
both sides of the 240 volt line for inrush current protection or
would a
single resistor of adequate size in one leg do the job? I am
speaking of
the typical amplifier running a pair of 3-500's.

Thanks,
Garry - WR4R



Yahoo! Groups Links





Yahoo! Groups Links


Re: "Father Measures"

pentalab
 

--- In ham_amplifiers@..., R L Measures <r@...> wrote:

RICH SEZ... Amen, however, some of my friends have told me I would
make a good priest. Maybe they were joking?...


### I can just see it now.... "Father Measures" ... up on the mound..
preaching a fire and brimstone lecture about..."parasitic hell"....to
us globar heathen's, with the ARRL bible in one hand.... and a wouf
hong ...made of solid Nichrome in the other hand. Quick... run for
your lives ! The sky is falling.

later... Jim VE7RF
R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


Results of removing grid fuse + cathode fuse

pentalab
 

OK, here's the deal.

I had my buddy with the 3x6 remove the fast 750 ma grid fuse from
the 3agc fuse holder... then try and apply 800w of drive. INPUT
SWR on the big amp goes sky high.... and then the IPA [87-A]
kicks itself offline..... leaving just the MK-V... which then see's
the same sky high swr.... and the yaesu MK-V of course throttles
back to zero watts output. .... good.

Grid fuse was re-installed.


Next up... the 3A 3agc cathode fuse was removed.

Again, 800w of drive applied. Exact same results..... sky high
input SWR... etc.

Note... the grid fuse results ONLY happen, if their is NOTHING
placed across the grid fuse holder.[no path for DC grid current, amp
can't be driven].

Originally we had a 100 K 3 w mof reistor in parallel with the
grid fuse holder. Upon grid fuse removal... and drive applied....
we were down to 2kw out... instead of the usual 12 kw. Input
swr went from 0 watts reflected, to 60 w reflected [800 w forward
= 8 % reflected.=low swr] We could also pull grid current.... but
a LOT less.

What was happening is this. The V drop across the 100 k mof
resistor [with grid fuse removed] was directly in parallel with
the reverse connected 6 A diodes... wired between chassis and B-
The V drop across the 100 k resistor turned on the diode.... and
grid current would flow via this new...alternate path.
Meanwhile, the V drop across the 100 K resistor was still being
applied to the cathode... and heavily biasing the amp into class
C.

So, the 100k resistor across the grid fuse ISNT'T needed.... don't
install it. Rich suggested a MOV in parallel with the grid fuse
holder. That's not needed either. The RVS connected diodes
between chassis and B- are STILL in parallel with the grid fuse
holder.

Later... Jim VE7RF


Re: Can a ..power factor correction cap be used on the input of a Plate Xfmr ??

pentalab
 

--- In ham_amplifiers@..., "craxd" <craxd@...> wrote:

Jim,

I've seen these used, but they were used in smaller DC supplies. I
have several books on the subject and will look it up.
### Yes.. pse do. It would be much appreciated as I have hit a
dead end here.


That value though seems way to much at 35 uF for this. Placed
across the primary leads, it will start looking like a short or a
leak if big enough.
That's why your seeing an increased current. The cap is causing
more current to be drawn or mag I + cap I.

#### My conclusion is... since pri current went from 1.8 A to
2.3A.... Cap current added another .5 A


All transformers have
magnetizing current which is low compared to their output power.
However, the larger the transformer, the more this will be. Also,
the
higher the flux density its ran at, the higher it will be.
### agreed. Point here is that we spend most of the time on RX...
and 2 A of magnetizing current = 480Va. Nothing we can do about
it. As far as power factor goes... that might be something we
can do something about. IF the correct size pwr factor cap can
be installed.... and the cap still draws current on RX.... then it
would be easy to switch out the cap on RX... with a vac relay.





For this type transformer service, the power factor should be
about 0.95 or so.

### I'd say the power factor on a large C input filter would be at
least .9 EG: u want to suck 900 w.... u need 1000 va. .9 x
1000 = 900w. Also 1000va/900w = 1.11 or 11% more primary
current required... due to power factor. Then you have to factor
in core losses.. another 10 %. So to convert DC input WATTS
to PRIMARY VA.... u gotta multiply dc input x 1.22 I
measured it... that's excatly what I get on a hypersil C core...
like atyp pole pig... or a Dahl product. On My 80 lb hammond
plate xfmrs [high reactance EI types... made for choke input....
but configured as a C input filter] you gotta multiply dc input
watts by 1.35 Other xfmr's are worse still.

### add more filter C... and power factor gets even worse still.




If the ripple is low where you want it, I wouldn't worry about
adding anything else that may draw more current.
### I'm fine with the ripple... it's under 1%. I'm worried about
the power factor.... and if something can be done.,.. great... if
not.... no big deal... since nobody is on TX for that long
anyway.... with vox/ roundtables etc.

## Being able to do something about 480 va CCS... caused by
magnetizing current would be nice. I suppose one could just
shut off the HV supply... if you knew you were gonna be on RX for
an hour... and just leave the fils on. Only a few seconds to get
the HV back online.... then ph Nuke station #6... and tell em to
pull the rods out.

Later..... Jim



Best,

Will


--- In ham_amplifiers@..., "pentalab" <jim.thomson@>
wrote:

Gents

My buddy tried this... said it worked. He gave me a 32 uf
cap
to
try it myself. It gets installed directly in parallel with
the
pri of the plate xfmr. [this is for a C input HV supply].

I didn't see any improvement... but I may well have easily had
the
wrong value. What I did notice was the magnetizing current
went
up on the pole pig... from 1.8A to 2.3A ! The magnetizing
current is why the step start never allows you to charge the
caps
up
to max V. [u always have current flowing through the drop
resistor]
The plate xfmr is always sucking magnetizing current... even
with
nothing connected to the secondary.

Dahl himself said the concept won't work. Seems to me it
would work on TX... and be the wrong value cap on RX...
because
of
load. The idea I had was to use a small possibly sped up vac
relay... tied into the T/R set up... to open/close... one leg of
the
cap.

I also noticed that the new 253 lb Dahl draws only 1.6 A of
magnetizing current. I thought it would be double that of the
smaller 120 lb pole pig.... it's not. The smaller pole pig
draws
1.8 A. My electrician buddy sez they never oversize vault
transformers... the idea being you don't want to be drawing
excess
magnetizing current.

I take it the magnetizing current is in addition to the normal
load ??

If my electrician buddy is correct... then why does the
bigger
Dahl draw LESS magnetizing current than the smaller 120 lb pole
pig ??

1.6 A is nothing to sneeze at... = 384 Va. 2.3 A = 552 Va

Magnetizing current is one thing.... power factor is another.
These
xfmr's typ have a .9 pwr factor... and even worse with a bigger
HV
C input filter. Maybe I'm confused here... but it appears the
load
is not the XL load of the xfmr... but the HV C filter on the
sec
side ?

Power factor correction caps work great on motor's and probably
xfmr's.. depending on the type of filter used.. C or resonant
choke.

Who's the expert on this ? Maybe Dahl is right.. and it
might
be
fruitless....... or maybe it works on TX... but correction cap
has
to be switched out on RX. IF it works... how do you go
about
sizing the correction cap ?.... and how much current flows
through
the correction cap ???

Later... Jim VE7RF


Re: ARRL - Political - was: Filament Voltage regulator

 

On Nov 12, 2006, at 5:42 PM, FRANCIS CARCIA wrote:


My next door neighbor growing up wanted to be a priest. In the late 60s he spent 3 years going to school then all of a sudden dropped out. I asked him why he changed his mind a couple years later. He told me he was afraid to go to bed at night for fear of who would join him. Sick.
In West Hollywood, this would be considered a perquisite.

None of this was news to me after learning that.
Church is too cheap to support priests who marry.
Correct, Frank, which is why they adopted the priestly vow of not to do women 9-centuries ago.

It is all about money (sick).
Law (Boston) should have also gone to jail but was promoted.
Right, and Bernard Law gets an allowance of c. $12,000 a month.
... ... ...
R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


Re: 3-500Z socket.... Johnson vs Eimac

pentalab
 

--- In ham_amplifiers@..., R L Measures <r@...> wrote:

RICH SEZ... The problem is that the 3-500Z air system socket
requires a high-pressure centrifugal blower, and Ham amps used an
ordinary centrifugal blower.

### See my note above. A 3-500Z only requires a .08" h2o
pressure.

RICH SEZ... Correct, but Eimac's 0.82" water column spec is the
pressure differential across the socket, and that usually means a
fairly noisy blower.

### The actual spec for a 3-500Z is 13 cfm @ .13" h2o...... or
26 cfm @ .13"... for a pair. And that's for 500/1000 w CCS
anode diss. Now .13" pressure is zip imo. Heck... the
requirements for a SINGLE 3CX-800A7 are 19 cfm @ .5" A 4CX-
250R is 6.4 cfm @ .59" A blower capable of .13" h2o is NOT
noisy. The puny blower in the L4B is dead quiet.. a lot quieter
than the 1" diam tiny fan in my outboard 30 vdc supply for the
yaesu MK-V. [the noise in the mk-v power supply is from the slots in
the cab... not the actual 1" diam fan]



RICH SEZ... That's how I do it. I also use a varnished cardboard
flap that hinges up to let the air out. It just doesn't look as
pretty.

### It would look like hell! Now that's what I call "K-mart
construction". Rich would call it part of his.. "ugly amplifier"
scene.
A square of varnished cardboard with two nickels glued to the
corners along one edge is light enough to rise automatically with
the airflow passing through an 8170. When the amp is off the
cardboard flops down, keeping spiders from constructing webs on the
insides.

### well, at least you got 2 x nickels to rub together !


### here's the interesting bit. Eimac states the glass tubes
cool by infared radiation.... well my natural gas fireplace puts
out loads of radiant heat.... a 3-500Z doesn't.
RICH SEZ... So objects that glow red-orange do not exhibit infra-
red radiation?

### If a 3-500Z is suppose to cool partially via infrared
radiation... I think they are full of it. I can put my hands on the
left side cabinet... [which is flat black... in and out]... and it's
stone cold... and also has zero air on it. You can take the cab
right off... and put ur hand [carefully] on the insides anywhere...
and feel no heat from the infrared radiation. The outsides of the
chimney's are hot [dead cxr, tubes red]... but that's from a lack
of air. The puny blower in the L4B is good for 600W CCS anode
diss... NOT 1kw. The point is.. the infrared radiation is not
heating anything else up in the cabinet. The Fluke 62 IR confirms
this.

### Another point here. The 3CX-800A7 has got 60% MORE anode
diss than a 3-500Z.... but only requires 46% more CFM than a 3-
500Z. So much for..."cooling" by infrared radiation.

### Rich... if you operated the SB-220 at 1500W out RTTY for 1
hr... you wouldn't have enough cooling on the tubes. You would
have to use a real noisy fan. [asuming a real pwr supply, and
loads of air on tank components... like that flaky bandswitch].
The point here is the fan set up in the SB-220 is designed for 600 w
out cw operation [400 w peak anode diss, 200 w CCS].... and 1200 w
pep out on ssb [800 w peak anode diss, maybe 400-500 W CCS]
that's it.... and that asumes you are not TX'ing all the time
either.

Later... Jim VE7RF

...
R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


Re: 3-500Z socket.... max current ratings

pentalab
 

--- In ham_amplifiers@..., Bill Turner <dezrat@...>
wrote:

All of Jim's points are valid and a good amp designer will take
them
into account. I would just caution anyone on adding an arbitrary
XX%
of airflow "just in case". If you are serious about your amp
design,
you should test the seal temperatures under any and all operating
conditions it may run into such as high altitude, dirty air
filters,
high ambient temperature, etc, etc. Only then can you be sure your
design will work under those conditions.

My point was, and is, that measurements of airflow, back pressure,
etc, are nice but what counts in the end is the temperature of the
tube seals. That is the weak point and that is why tube
manufacturers
specify a maximum value. If a designer ONLY measures airflow and
ignores seal temp, he is asking for trouble down the road.

I realize for most of us homebrewers that isn't really practical to
perform all those tests in all cases, but we should try to come as
close as we can.
### Highly agreed. Seal temperature is the final determining
factor. Use of temperature sensitive paints are easy to use...
they are well documented in care and feeding and other
literature... they will melt and turn cystaline, when the pre-set
temp is exceeded. Due to the normal chimney setups... even my
Fluke mini 62 can't be pointed at the seals... only the portion of
the metal anode above the chimney.... which is nice to know.... but
not what we really want to know. On a glass tube... a Fluke 62
will work fine on the top seal. However,you still can't get at the
bottom pins/seals very easily.

Later... Jim VE7RF

Bill, W6WRT




------------ ORIGINAL MESSAGE ------------On Sun, 12 Nov 2006
13:21:24
-0000, "pentalab" <jim.thomson@...> wrote:

<snip>

### I wouldn't say that just because XXX amount of airflow
provides say 249 deg C.... that that is good enough. Eimac
bases
their airflow specs on 225 deg C.. allowing a 25 deg C "safety
factor". You also have to allow for dirty air filters,
partially clogged anode fins, etc. Most designers of
commercial
gear [ real broadcast gear... not Ameritron ham stuff] will take
the Eimac pressure requirements... and add 20% right off the
bat.
That will factor in ducting from blower to plenum... and also
dirty
air filters, right angle bends etc.
<snip>


Re: Inrush filament current protection

pentalab
 

--- In ham_amplifiers@..., "Robert B. Bonner"
<rbonner@...> wrote:

Garry,

That is a great question. I have a couple projects going together
RIGHT NOW that had me thinking the same thing.

It depends on if you cheat or not.
### huh ? AS long as you have a relay/contactor/ ckt breaker that
opens OFF BOTH sides of the 240v line... anything beyond that is
a moot point...and legal. BEWARE... if using fuses on the
primary.... they HAVE to be 240 V rated... NOT 120 V rated.
Here's why. IF only one fuse in one leg of the primary blew
open... and the 2nd fuse in the other leg was intact....you could
end up in a situation where 120 v is fed to one side of the plate
xfmr primary.... where it will simply pass throught the typ .08 ohm
dc resistance primary... then back to the OUTPUT side of the blown
fuse.[call this leg #2] Meanwhile... on the INPUT side of the
blown fuse.... you still have 120 V [coming from leg #1.] The
potential difference across the blown fuse in leg #1 will
be ...240 V. IE: with EITHER fuse blown [but only one], you
will have 240 v across an open fuse.... so DON'T use 120 V rated
fuses in either leg of a 240 v LINE.

### ALSO BEWARE.... some amps like the L4B... use two SEPARATE
circuit breaker's... one per hot leg... and NO tie bar between
em. These are usually the type that resemble a 3agc fuse
holder.When these type of breakers open up... they extend outwards.


OK what does that mean? 220V wiring is 2 wire plus ground, not 2
wire plus neutral.

### partially agreed. ALL wire now comes with a bare or
insulated grnd...whether u want it or not. The grnd is NEVER
considered any more in the wire count. So, you either
ask/order 2 conductor wire.... OR 3 conductor wire. 2 x
conductor wire comes with a grnd... so total wires = 3. 3 x
conductor wire also comes with a grnd... so total wires = 4. IE:
you ask fo 3 x wire XXX ga.... u get a total of 4 x conductor's.




If you use legal by code 220/221V (whatever it takes) building
practices you could get by with only 1 resistor in the step start.

#### The electrical code will state on a 240 v circuit you will
require a TWO pole breaker..and/or a TWO pole relay/contactor...
to open off BOTH sides of the line. After that.. they could care
less if u install a 12.5 ohm resistor in EACH hot leg... or a 25 ohm
resistor in just ONE hot leg. Putting a resistor in both legs is
a waste of effort. It's total LOOP resistance we are concerned
with here.




If you cheat and have some 110 volt circuitry in the amplifier
like a filament transformer that runs on 110 you would want to have
2 resistors in the step start.

### Agreed. BUT.... on an amp like the L4B.. and 99% of em...
that have a SEPARATE fil xfmr.... the fil xfmr will ALWAYS have
it's own dual 120 v primary's.... which can be wired in parallel
for 120v... or in series for 240 V. The only exception to
this.. would be if in a condo with 208/120V wiring per suite.
You can then run 208 V into the plate xfmr [wired for 240V.. so u
end up with slightly less plate V].... and run 120 V to the fil
xfmr [wired for 120V... so fil gets correct V]

### IF, indeed one had a fil xfmr that ONLY ran on 120v.... then,
you would have to ensure that the hot leg feeding the fil xfmr..
came from the SAME side of the 240 v line.... as your single
step start resistor.... so when step started... you step start BOTH
the HV supply AND the fil xfmr... at the same time...from the same
source.



In this situation you would have current flow on the GROUND LEAD.
### No you wouldn't. That could only happen if one side of the
120V fil xfmr [or any other 120 v device] was tied directly to
the chassis.. instead of the neutral. That isn't going to happen..
since it's not allowed... would violate every electrical code in
North America. On a similar note... you NEVER bond the neutral to
the chassis.... that also violates every electrical code in NA.
The ONLY thing bonded to the chassis is the grnd wire. With any
shorts from either side of line to chassis... the grnd wire
handles the full fault current.

### On circuits which require a huge 240 V load... like a HV
supply.... but only a tiny load for the 120 V load... like say a
120 V blower... some tiny xfmr's for a T/R supply, etc... then
it would be ok to use a smaller neutral.... as long as the neutral
could handle the entire fault current... IF a line to neutral
short occured. EG: 2 ga wire for each hot leg... and a 100 A
main breaker in panel... but only 6 ga wire for the neutral....
and also 6 ga wire for the grnd.



That's why professional grade equipment has a 220 - 110 step down
transformer on board.
### You see that in the Henry 8 k manual. They do that to run
the 120 v Dayton blower. In EU/UK... they don't use a 3 wire 220
v line. They only have 2 x wires from the pole pig... with 220 v
across em. One side of the line is bonded to earth ground... so
one leg is hot... the other leg is valled neutral. That way, they
only have to fuse the ONE hot leg... and any switches, relays,
etc, are only required to be single pole types... for the one hot
leg. As per the 8K... when you look up the Dayton blower part
number they spec in their parts list in their manual.... and cross
reference it to the Dayton blowers on Grainger's website... turns
out it's the 230 V version of the same blower... and in fact, the
240/120 V step down xfmr shown in the schematic and also the picture
drawings.... doesn't exist.

## Notice on 240 V clothes dryers... they always include a
neutral... to run the 120 V blower. Seems stupid to me. They
shoulda just used a 240v blower... and could have eliminated the
requirement for a neutral..... just like a 240 v hot water
tank.... none of which have a neutral... since the heating els run
on 240 V only.




Another option is 4 wire circuitry where you have 220
plus neutral and ground. What a pain with the outlets etc...
### what's the problem with the outlets ??? A 30 A dryer
outlet comes with 2 x hots, one neutral... one gound. A 40 A
stove is exactly the same thing. Ditto with 20 A circuits.




A guy should follow good construction practices. BUT for home
brewing does it really matter? NAW it will turn on and work.

### with HB HV supplies... you don't need an outlet. You just
hardwire the 2 ga wire directly to the line side input of the
front or rear panel mounted breaker. OR hardwire the 2 ga wire
directly to the jumbo contactor input..... either way... you still
have the breaker in the main panel that feeds this mess. You can
buy 75/100/150/200 A outlets... cost a small fortune. You don't
need em.... just hardwire the big wire in..... and when working on
the amp.... kill the breaker in the main panel. IF the HV
supply/amp needs to be rolled over to the bench... just
disconnect the 4x wires at the HV/amp end.




Just an FYI, I use a double resistor. It just happens to look
prettier, double pole relay, pair of resistors, double pole relay
all in line. Nice pretty yellow adjustable time delay relay.

### Here's what I do. I use 25 ohms in one leg only... and only
one contactor to short out the resistor. The kicker is.. I use a
pair of paralled 50 ohm resistor's to make up the 25 ohms ! If
one resistor ever opened up... the 2nd one [albeit 50 ohms] is
still in the circiut. That way... I can never shunt an open single
resistor with the step start contactor... and slam a huge load on
the diodes.... IE: no step start at all... which would be a
disaster with 100-200 uf C input filter. These large metal
finned resistor's you see made by DALE and other's, works
perfectly for the step start R. Just bolt it to metal chassis
anywhere. Cuz of our magnetizing current.... I use a min of a 100w -
200 W rated units... EACH. You will have the entire 240 V
dumped across em when you 1st hit the switch. When everything
settles down... I still have 2 A of magnetizing current flowing
through em..[100/200 w]... then they get shunted.

## I also use the yellow /white adjustable Time delay relay. The
TD relays are all DPDT 10 A contacts.... which are used to
activate the coil of the step start contactor. The big step
start contactor has loads of AUX contacts... which are wired to
the amp key line.... ditto with main incoming contactor.... so
you can't key the amp unless all the contactor's are actually
operated. We use loads of 120 v neons as well.. status lamps...
to tell us instantly, where a problem is.. works slick.. if and when
it comes time to trbl shoot anything. A row of 3agc fuses [and
more neons on the output sides of the fuses] are the various feeds
for the blower, TD relays, small xfmr's for T/R relays, contactor's
etc.

### On the big stuff.... we use a separate Time delay for the fil
xfmr... which has it's own step start resistor/ variac, etc. The
fil TD is set for 8-10 seconds.... the HV delay is set for 15-
25 seconds. The blower over run TD is set for 15 mins.

-also have an airflow vane/ switch, retrofitted inside the blower.
Contacts of the airflow switch are wired to the coil of a small
relay.... whose contacts open off the 240 V to the fil xfmr.
The last thing you want is no air to a tube... esp when it's 30'
away... in another room. The slick thing about this setup is...
IF the commercial AC power goes off.... everything shuts down.
When the power comes back on.... everything just goes through it's
normal step start sequence etc. You can't key the amp... until
it's all finished.

Later... Jim VE7RF

BOB DD

-----Original Message-----
From: ham_amplifiers@...
[mailto:ham_amplifiers@...]
On Behalf Of Garry Drummond
Sent: Sunday, November 12, 2006 9:29 AM
To: ham_amplifiers@...
Subject: [ham_amplifiers] Inrush filament current protection

When running an amp on 240 volts, is it necessary to put a
resistor in
both sides of the 240 volt line for inrush current protection or
would a
single resistor of adequate size in one leg do the job? I am
speaking of
the typical amplifier running a pair of 3-500's.

Thanks,
Garry - WR4R



Yahoo! Groups Links


Re: ARRL - Political - was: Filament Voltage regulator

FRANCIS CARCIA
 

My next door neighbor growing up wanted to be a priest. In the late 60s he spent 3 years going to school then all of a sudden dropped out.?I asked him why he changed his mind a couple years later. He told me he was afraid to go to bed at night for fear of who would join him. Sick. None of this was news to me after learning that.
Church is too cheap to support priests who marry. It is all about money (sick).
Law (Boston)?should have also gone to jail but was promoted.

R L Measures wrote:


On Nov 11, 2006, at 5:27 AM, pentalab wrote:

> --- In ham_amplifiers@yahoogroups.com, R L Measures wrote:
> >
> >
> > On Nov 11, 2006, at 12:27 AM, pentalab wrote:
> >
> > > --- In ham_amplifiers@yahoogroups.com, R L Measures
> wrote:
> > > >> > ### Interesting. Per a 2 hr documentary on A+E... the church
> > > coughed up 600 million cash.. for families of victims.... for
> > > exactly 600 x priest's. All were settled out of court.
> >
> > RICH SEZ...So far, over $1100-million has been paid out in the
> U. S. and the Los Angeles archdiocese has yet to settle with the
> 600+ victims of its 170+ pedo- priests. Two of my friends were
> victims. . . trivia: Archbishop of L.A., Roger Mahony's
> callsign is W6QYI.
> > >
> ### U gotta be kidding ? $1100- million is 1.1 BILLION BUX

Correct. That a stack of Ben Franklins 44,000 inches high.
>
> ! Now u know where the money goes every week. My older sis thinks
> it's all hogwash... "they couldn't possibly have done any of it"...
> and they must be nothing but..."unsubstantiated allegations" by a
> bunch of witch hunting sour grapes types.

Take the case of Fr. Paul Shanley. His defense attorneys argued
unsuccessfully that he was unfairly seduced by a cute six-year old boy.
> The trbl is.... even
> though $1100 million has been paid out of court.

The total includes in court as well as out of court settlements -
a.k.a., "hush-money". Thus, the total is an estimate made by
attorneys who litigate such cases.

> ... meanwhile these
> pedo-priest's are still running amuck...free. You only hear of
> the odd one being locked up.... if they can find him.
>
> ### so what do you think is the real problem ? Is is the Priest's
> vow of celibacy.... and/or that they can't marry.... or is the
> church a magnet for nut cases ?

That's a question with a complex answer. As I see it, if they have a
job rule that priests can't do it with women, odds are that those men
who do not want to do it with women will be interested in the job.
>
> ### I'd be embarassed to belong to a bozo run outfit like that.

Amen, however, some of my friends have told me I would make a good
priest. Maybe they were joking?...
>

R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org



Re: Inrush filament current protection

craxd
 

For the life of me, I can't figure out why you would need one for
each line lead? If the voltage drops, the current rises making the
same output power from the transformer. The same amount of power will
be drawn either way if the amps output is the same. Example, 220Vac x
14 amperes is 3,080 watts, and 110 Vac x 28 amperes is 3,080 watts. A
25 ohm resistor at 110 Vac or 220 Vac would see the same power in
watts since when the voltage drops, the current rises, and when
voltage rises to 220 vac, current drops by 1/2. Does the surge
current increase more than double by dropping the voltage down to 110
Vac? The only difference in the primary windings are having them
either in series or parallel.

Thanks,

Will

--- In ham_amplifiers@..., R L Measures <r@...> wrote:


On Nov 12, 2006, at 7:29 AM, Garry Drummond wrote:

When running an amp on 240 volts, is it necessary to put a
resistor in
both sides of the 240 volt line for inrush current protection or
would a
single resistor of adequate size in one leg do the job? I am
speaking of
the typical amplifier running a pair of 3-500's.
Amplifiers that run on two voltages need two step-start resistors,
but those that run on one V need only one

Thanks,
Garry - WR4R

R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


Re: Can a ..power factor correction cap be used on the input of a Plate Xfmr ??

craxd
 

Jim,

I've seen these used, but they were used in smaller DC supplies. I
have several books on the subject and will look it up. That value
though seems way to much at 35 uF for this. Placed across the primary
leads, it will start looking like a short or a leak if big enough.
That's why your seeing an increased current. The cap is causing more
current to be drawn or mag I + cap I. All transformers have
magnetizing current which is low compared to their output power.
However, the larger the transformer, the more this will be. Also, the
higher the flux density its ran at, the higher it will be. For this
type transformer service, the power factor should be about 0.95 or
so. If the ripple is low where you want it, I wouldn't worry about
adding anything else that may draw more current.

Best,

Will


--- In ham_amplifiers@..., "pentalab" <jim.thomson@...>
wrote:

Gents

My buddy tried this... said it worked. He gave me a 32 uf cap
to
try it myself. It gets installed directly in parallel with the
pri of the plate xfmr. [this is for a C input HV supply].

I didn't see any improvement... but I may well have easily had the
wrong value. What I did notice was the magnetizing current went
up on the pole pig... from 1.8A to 2.3A ! The magnetizing
current is why the step start never allows you to charge the caps
up
to max V. [u always have current flowing through the drop resistor]
The plate xfmr is always sucking magnetizing current... even with
nothing connected to the secondary.

Dahl himself said the concept won't work. Seems to me it
would work on TX... and be the wrong value cap on RX... because
of
load. The idea I had was to use a small possibly sped up vac
relay... tied into the T/R set up... to open/close... one leg of
the
cap.

I also noticed that the new 253 lb Dahl draws only 1.6 A of
magnetizing current. I thought it would be double that of the
smaller 120 lb pole pig.... it's not. The smaller pole pig draws
1.8 A. My electrician buddy sez they never oversize vault
transformers... the idea being you don't want to be drawing excess
magnetizing current.

I take it the magnetizing current is in addition to the normal
load ??

If my electrician buddy is correct... then why does the bigger
Dahl draw LESS magnetizing current than the smaller 120 lb pole
pig ??

1.6 A is nothing to sneeze at... = 384 Va. 2.3 A = 552 Va

Magnetizing current is one thing.... power factor is another.
These
xfmr's typ have a .9 pwr factor... and even worse with a bigger HV
C input filter. Maybe I'm confused here... but it appears the
load
is not the XL load of the xfmr... but the HV C filter on the sec
side ?

Power factor correction caps work great on motor's and probably
xfmr's.. depending on the type of filter used.. C or resonant
choke.

Who's the expert on this ? Maybe Dahl is right.. and it might
be
fruitless....... or maybe it works on TX... but correction cap has
to be switched out on RX. IF it works... how do you go about
sizing the correction cap ?.... and how much current flows through
the correction cap ???

Later... Jim VE7RF


Re: ARRL - Political - Hiram Percy maxim

craxd
 

Hirams Percys father, Hiram Stevens Maxim was the daddy of the Maxim
machine gun that helped cause all the carnage in WWI. Though the
Browning machine gun eventually won out during US government testing,
the Maxim was still used in Britan. It went out of production though
and became the Vickers machine gun. The size came down and others had
increased capacity like the Thompson "Tommy" gun. This was the mobs
favorite in the 20's. The same Browning 30 and 50 cal's are still
being produced and used today. The Vickers was used up to 1968 by
Britan.

I would think that dealing out death ran in the Maxim family. The
first way was quickly, and the second silently.

Hiram Stephens brother Hudson Maxim was also a military inventor,
specializing in explosives. Again, a death dealer.

Just because Hiram Percy was one of the founders of the ARRL, doesn't
hide his family history.

Best,

Will

--- In ham_amplifiers@..., R L Measures <r@...> wrote:


On Nov 12, 2006, at 3:48 AM, pentalab wrote:

--- In ham_amplifiers@...,

RICH SEZ... opposite page (p.9) there's a picture of the inventor
of
the firearms silencer, Hiram P. Maxim, wearing a set of
headphones -
but strangely he is given no credit whatsoever for his brilliant
invention.

#### Hiram Percy Maxim DIDN'T invent the silencer.... his FATHER
did.
Not according to history, Jim.
..per "200 metres and down". His father was on this noise
abatement program.... and came up with ways to quieten down
everything
from air conditioners to cars.. planes etc. He didn't like the way
the noise level was rising in the cities. His next step was guns.
His 1st silencer was for shot guns... sort of like an acoustical
mechanical notch filter. They had to know how many grains the
projectiles were.. the freq, velocity, etc. The 1st shot gun
silencers sold for just $7.00 . Organized crime types apparently
wanted em real bad. Wonder how many people got knocked off from
his
invention?


"Hiram Percy Maxim
born Sept. 2, 1869, Brooklyn, N.Y., U.S.
died Feb. 17, 1936, La Junta, Colo.
American inventor and manufacturer known especially for the
"Maxim
silencer" gun attachment. Son and nephew of famous inventors,
Maxim
graduated from Massachusetts Institute of Technology, then in
Boston,
at age 16 ..."

The thing that some people don't realize about silencers is that
they
do not silence the sonic crack of a bullet traveling faster than
the
speed of sound (c. 1060 feet per second), so even a 22-LONG RIFLE
equipped with a silencer still makes a lot of racket. Also, Maxim-
silencers are useless on any revolver since a stentorian blast
exits
out the side from the gap between the receiver and the cylinder.
Thus, in "The Godfather" series, Vito Corleone expertly wraps a
towel
around the revolver to muffle the cylinder gap noise as well as
the
muzzle-blast when he terminates the neighborhood asshole.

Shotgun silencers would be more like mufflers because the
pellets
typically leave the barrel about 300-ft-sec above the speed of
sound.
### Here's a question. Can one still be an ARRL life member ??
The last I heard, yes.
As
in.... pay XXX dollars. Im talking about today....now.

### My buddy is an ARRL lifer. I'm sure it cost him something
bizzare like a few hundred bucks... back in 1976. Thought it was
like
$500.00 to $750.00

Later.... Jim VE7RF
R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


Re: Inrush filament current protection

 

On Nov 12, 2006, at 7:29 AM, Garry Drummond wrote:

When running an amp on 240 volts, is it necessary to put a resistor in
both sides of the 240 volt line for inrush current protection or would a
single resistor of adequate size in one leg do the job? I am speaking of
the typical amplifier running a pair of 3-500's.
Amplifiers that run on two voltages need two step-start resistors, but those that run on one V need only one

Thanks,
Garry - WR4R

R L Measures, AG6K, 805.386.3734
r@..., rlm@..., www.somis.org


Re: Inrush filament current protection

Robert B. Bonner
 

Garry,

That is a great question. I have a couple projects going together RIGHT NOW
that had me thinking the same thing.

It depends on if you cheat or not.

OK what does that mean? 220V wiring is 2 wire plus ground, not 2 wire plus
neutral.

If you use legal by code 220/221V (whatever it takes) building practices you
could get by with only 1 resistor in the step start.

If you cheat and have some 110 volt circuitry in the amplifier like a
filament transformer that runs on 110 you would want to have 2 resistors in
the step start.

In this situation you would have current flow on the GROUND LEAD.

That's why professional grade equipment has a 220 - 110 step down
transformer on board. Another option is 4 wire circuitry where you have 220
plus neutral and ground. What a pain with the outlets etc...

A guy should follow good construction practices. BUT for home brewing does
it really matter? NAW it will turn on and work.

Just an FYI, I use a double resistor. It just happens to look prettier,
double pole relay, pair of resistors, double pole relay all in line. Nice
pretty yellow adjustable time delay relay.

BOB DD

-----Original Message-----
From: ham_amplifiers@... [mailto:ham_amplifiers@...]
On Behalf Of Garry Drummond
Sent: Sunday, November 12, 2006 9:29 AM
To: ham_amplifiers@...
Subject: [ham_amplifiers] Inrush filament current protection

When running an amp on 240 volts, is it necessary to put a resistor in
both sides of the 240 volt line for inrush current protection or would a
single resistor of adequate size in one leg do the job? I am speaking of
the typical amplifier running a pair of 3-500's.

Thanks,
Garry - WR4R



Yahoo! Groups Links


Inrush filament current protection

Garry Drummond
 

When running an amp on 240 volts, is it necessary to put a resistor in both sides of the 240 volt line for inrush current protection or would a single resistor of adequate size in one leg do the job? I am speaking of the typical amplifier running a pair of 3-500's.

Thanks,
Garry - WR4R


Re: 3-500Z socket.... max current ratings

Bill Turner
 

All of Jim's points are valid and a good amp designer will take them
into account. I would just caution anyone on adding an arbitrary XX%
of airflow "just in case". If you are serious about your amp design,
you should test the seal temperatures under any and all operating
conditions it may run into such as high altitude, dirty air filters,
high ambient temperature, etc, etc. Only then can you be sure your
design will work under those conditions.

My point was, and is, that measurements of airflow, back pressure,
etc, are nice but what counts in the end is the temperature of the
tube seals. That is the weak point and that is why tube manufacturers
specify a maximum value. If a designer ONLY measures airflow and
ignores seal temp, he is asking for trouble down the road.

I realize for most of us homebrewers that isn't really practical to
perform all those tests in all cases, but we should try to come as
close as we can.

Bill, W6WRT




------------ ORIGINAL MESSAGE ------------On Sun, 12 Nov 2006 13:21:24
-0000, "pentalab" <jim.thomson@...> wrote:

<snip>

### I wouldn't say that just because XXX amount of airflow
provides say 249 deg C.... that that is good enough. Eimac bases
their airflow specs on 225 deg C.. allowing a 25 deg C "safety
factor". You also have to allow for dirty air filters,
partially clogged anode fins, etc. Most designers of commercial
gear [ real broadcast gear... not Ameritron ham stuff] will take
the Eimac pressure requirements... and add 20% right off the bat.
That will factor in ducting from blower to plenum... and also dirty
air filters, right angle bends etc.
<snip>